Variable frequency drive leakage current

In I/O cables and motors of a variable frequency drive (VFD), the stray capacitance C is present. High-speed switching in the main circuit lets the leakage current flow from the stray capacitance C to the ground. The amount of the leakage current differs depending on the stray capacitance C, carrier frequency, etc. Accordingly, the low-noise type variable frequency drives generate the larger leakage current.

Effects of leakage current
1) The leakage breaker or leakage relay may operate unintentionally due to the leakage current between grounds. The leakage current includes many high frequency components that have a relatively small influence on human body.
2) The external thermal relay may operate unintentionally due to the leakage current between cables.
VFD leakage current

Measures
  • Decrease the carrier frequency of the variable frequency drive. (Note that doing so causes a louder motor noise.)
  • Install leakage breakers designed for the harmonics and surge suppression to the variable frequency drive's own system and other system. (Switching speed does not have to be decreased.)
  • Decrease the stray capacitances between grounds. (Use cables or wires that are insulated with materials of low relative permittivity.)
Selecting a leakage breaker
Select a leakage breaker designed for the harmonics and surge suppression. The main task of a current circuit breaker or a current protection device in general is to interrupt a circuit in the event of a variable frequency drive malfunction. The electronic switch measures the incoming and outgoing current of a device or system. If it establishes that these two currents are not identical, it will interrupt the circuit, as the current flow has (possibly) taken a hazardous direction somewhere - due to an insulation failure.

This current can be caused by a person touching a conductor and the body of this person directing the circuit towards the earth. The current circuit breaker protects the person by very quickly interrupting the circuit, thereby preventing any further injury.

Post a Comment:

    
Plz Calculate (3 + 5) =
(Your comment will show after approved.)

You may also like:

Category
Featured Articles
Variable Frequency Drive Sizing Variable Frequency Drive SizingBefore selecting the size of a variable frequency drive (VFD), it is necessary to generally know the working environment, the ...
Single VFD for Multiple Motors Single VFD for Multiple MotorsA single variable frequency drive (VFD) may control 2 or 3 motors at a time, multiple motors control is usually done because of ...
PWM Variable Frequency Drive ... PWM Variable Frequency Drive CharacteristicsPulse Width Modulation (PWM) voltage source variable frequency drives (VFD) presently comprehend the most used equipments to feed ...
Variable frequency drive for water ... Variable frequency drive for water pumpsQuantifying the energy efficiency of pump units across markets is a tough task: These units mostly consist of rotodynamic pumps ...
Variable Frequency Drive Basic Safety ... Variable Frequency Drive Basic Safety GuidelinesThis paper provides guidelines on functional safety considerations when selecting and integrating a variable frequency drive ...
service
Variable Frequency Drives control AC motor for energy savings by adjustable speed, for short VFD, also named variable speed drives and frequency inverter.